ru en
PLK 3000 controller

PLK 3000 controller

The PLC 3000 performs the functions of monitoring and controlling local equipment, and communicating with the dispatch control level and with other units of the complex. The controller can be reconfigured to expand its functionality by adding expansion modules.
The PLK 3000 controller supports the following information protocols for various communication interfaces: TCP, UDP, IP, PPP, NTP, DHCP, Modbus RTU, IEC 60870-5-101 / 104.
All modules support the "lock" mode, in which all module outputs take a predetermined state in the event of a specific blocking signal.
The PLK 3000 supports various power saving modes: disabling unused components, reducing performance to reduce power consumption, sleep modes.
The PLK 3000 can accomodate:
  • up to 592 discrete input/output lines;
  • up to 288 analog I/O lines;
  • up to 100 lines of serial interfaces RS232, RS485;
  • up to 74 twisted pair Ethernet channels;
  • up to 24 fiber optic Ethernet channels.
The PLK 3000 software is updated via data interface: debugging RS232; Ethernet; Wi-Fi (ad-hoc mode).

Signature features:

Ultra Low Power Consumption
Flexible control of power supply for system components
Can be configured for automation systems of varying complexity
Modular design, maximally adaptable to equipment in order to create automation systems of varying complexity
Incorporates the IEC engineering languages
High information capacity
Natural cooling of module elements
The controller’s design provides natural cooling of the module elements
Operates in a wide ambient temperature range: -60 to +60°C
Protected against accidents
Support for secure communication
Support for secure communications over industrial networks and Ethernet

Characteristics

Analog I/O Channels
inputs from 0 to 5 mA, from 4 to 20 mA, from 0 to 20 mA, from 0 to 10 V with the function of recognition of line open/shorts - up to 1296 pcs (if using three crates and the maximum number of modules with this type of I/O channel)
outputs from 0 to 5 mA, from 4 to 20 mA, from 0 to 20 mA, from 0 to 10 V - up to 864 pcs. (if using three crates and the maximum number of modules with this type of I/O channel)
Discrete I/O channels
"potential" inputs: up to 1726 (plus 16 digital triggering inputs for emergency protection), if using three crates and the maximum number of modules with this type of I/O channel
voltage-free inputs: up to 576 (if using three crates and the maximum number of modules with this type of I/O channel)
"transistor switch" outputs: up to 584 (if using three crates and the maximum number of modules with this type of I/O channel)
"relay" outputs: up to 864 (if using three crates and the maximum number of modules with this type of I/O channel)
Types of communication interfaces
RS-485 - up to 100
RS-232 - up to 100
Fast Ethernet 10/100BASE-TX - at least 2 (determined by the number of installed Ethernet switches)
Fast Ethernet 100BASE-FX - determined by the number of installed Ethernet switches
802.11b/g Wi-Fi (only for communication with the user's PC during debugging or configuration) - 1
Controller options by backup type
No backup
CPU Module Backup
Full backup of controller modules
Maximum overall dimensions (for one crate), mm, max
485x266x200
Maximum weight of one crate, kg, max
16
Permissible range of input direct current voltage (without external power supply from 220 V network), V
DC from 10 to 32
Allowable range of input AC power supply voltage when using external power supply from 220 V network (determined by power supply parameters), V
AC from 100 to 240
Permissible range of the AC power supply voltage frequency when using an external power source from the 220 V network (determined by the power supply parameters), Hz
47 to 63
Maximum power consumption
Determined by the operation and the types of installed modules
Operating temperature range, ºC
-40 to +60
optional -61 to +60
Transport/storage temperature, ºС
-61 to +60
Relative humidity, (at a temperature of +25 ºC),%
5 to 95 without condensation
Atmospheric pressure, kPa
84 to 106.7
Resistance to high frequency sinusoidal vibrations
N2 (according to GOST R 52931-2008)
show all Characteristics

Configuration*

When delivered, the PLK3000 can be equipped with external power supplies of the following types (depending on the power consumption): LWN2660-6E: 125W, LWN1601-6E: 250W, DPP240-24-1: 240W, DRA240-24A: 40W, and WDR-240-24: 240W.
show package contents
Description and brief technical specifications
CPU
CPU module. Includes an IM interface module with a mezzanine board MPP-287 installed on it (KRAU4.883.308)
IM
Interface Module
RSSW-8
RS-232/RS-485 serial port switching module
ESW-6C2F
Fast Ethernet switch module for 6 10/100BASE-TX "copper" ports and 2 100BASE-FX "optic" ports
CR-2012
Crate with one slot for central modules and 12 slots for expansion modules with installed CrossBoard
CR-2009
Crate with one slot for the central modules and nine slots for expansion modules with the installed CrossBoard
CR-2007
Crate with one slot for central modules and 7 slots for expansion modules with installed CrossBoard
CR-2005
Crate with one slot for central modules and 5 slots for expansion modules with installed CrossBoard
CR-2003
Crate with one slot for central modules and 3 slots for expansion modules with installed CrossBoard
DIO-16
This module contains 16 digital I/O channels; Two pulse counters that can be set to any of the input channels; Individual galvanic isolation for each channel; Output type: semiconductor; Input types: "potential" and voltage-free; powered from the module
AIO-8
This module contains 8 analog input channels and 8 analog output channels; Individual galvanic isolation for each channel; Measuring range 4 to 20 mA
DO16-24AD
This module contains 16 digital output channels; Individual galvanic isolation for each channel; Output type: electromechanical relay; Switching current - up to 2 A (30 V AC\DC)
DO24-24AD
This module contains 24 digital output channels; Individual galvanic isolation; Output type: semiconductor; Switching current - up to 2 A (30 V AC\DC)
DO32-24AD
This module contains 32 digital output channels; Galvanic isolation: 8 groups of 4 outputs; Output type: semiconductor; Switching current - up to 0,5 A (30 V AC\DC)
DO48-24AD
This module contains 48 digital output channels; Galvanic isolation: 2 groups of 24 outputs; Output type: semiconductor; Switching current: up to 0.1A (30 V AC\DC)
DO8-110DC-PWR
This module contains 8 digital power output channels; Galvanic isolation: 2 groups of 4 outputs with internal power supply of each group 110 V; With an output power limitation per each group of 30 W
DO16-220AD
This module contains 16 digital output channels; Individual galvanic isolation for each channel. Output type: electromechanical relay; Switching current: up to 2 A (220 V AC) up to 0.28 A (220 V DC)
DO16-220AС
This module contains 16 digital output channels; Individual galvanic isolation; Output type: semiconductor; Switching current: up to 2 A (220 V AC)
DO16-220DС
This module contains 16 digital output channels; Individual galvanic isolation for each channel; Output type: semiconductor; Switching current: up to 1 A (220 V DC)
DI32-24
This module contains 32 digital input channels; Galvanic isolation: 8 groups of 4 inputs. 24V AC\DC, 10mA; Counters up to 12 kHz with 8 channels
DI48-24
This module contains 48 digital input channels; Galvanic isolation for a group of inputs from the grounding and controller power supply bus. 24V AC\DC, 10mA; Counters up to 12 kHz with 8 channels
DI12-24-F
This module contains 12 fast counters; Frequency measuring range: from 0.5 to 100,000 Hz
DI24-220
This module contains 24 digital input channels; Individual galvanic isolation. 220V AC\DC, 10mA
AI16-IU
This module contains 16 analog input channels; Individual galvanic isolation for each channel; Measuring ranges: from 0 to 5 mA, from 0 to 20 mA, from 4 to 20 mA, from 0 to 5 V, from 0 to 10 V, from -5 to +5 V, from -10 to +10 V
AI32-24
This module contains 32 analog input channels with individual galvanic isolation; Galvanic isolation 4 groups of 8 inputs. Measuring ranges: from 0 to 5 mA, from 0 to 20 mA, 4 to 20 mA
AO12-IU
This module contains 12 channels for outputting DC signals; Individual galvanic isolation for each channel. Ranges: from 0 to 5 mA, from 0 to 20 mA, from 4 to 20 mA, from 0 to 5 V, 0 to 10 V
AI6O6-IU-Hart
This module contains 6 channels of input and output of analog signals of direct current and DC voltage; Supports data transfer using Hart protocol; Individual galvanic isolation for each channel; Ranges: from 0 to 5 mA, from 0 to 20 mA, from 4 to 20 mA, from 0 to 25 mA, from -5 to +5 V, from -10 to +10 V
AIT12
This module contains 12 channels for the input of analog DC signals from resistance thermometers and thermocouples; Individual galvanic isolation for each channel; Ranges: from 0 to 5 mA, from 0 to 20 mA, from 0 to 5 mA, from 0 to 10 mV, from 0 to 50 mV, from 0 to 100 mV, from 0 to 500 mV, from -10 to +10 mV, from -50 to +50 mV, from -100 to +100 mV, from -500 to +500 mV, from 0 to 5 V, from 0 to 10 V, from -5 to +5 V, from -10 to +10 V; Sensor types: resistance temperature transducers (in conformance with GOST 6651); thermocouples (in conformance with GOST R 8.585-2001)
AI6_SOU
This module contains 6 channels for the input of analog DC signals; Designed for use in a leak detection system; Measuring range: 4 to 20 mA; Built-in algorithms for detecting pressure waves in a pipeline and determining their direction
* may be altered. Clarified at the time of order
show package contents